## 1. A technician is recovering refrigerant from a medium-pressure appliance with a full charge of 350 pounds. The recovery machine was manufactured in 2018. To what level must the technician evacuate the appliance?
- A. 15 inches of Hg vacuum
- B. 4 inches of Hg vacuum
- C. 25 mm Hg absolute
- D. 10 inches of Hg vacuum

Answer: A. Medium-pressure appliances with a full charge of 200 pounds or more must be evacuated to 15 inches of Hg vacuum when the recovery equipment was made on or after November 15, 1993. The 4-inch level applies only to equipment made before that date. The 10-inch level is for medium-pressure systems under 200 pounds, and 25 mm Hg absolute is the low-pressure requirement.
Source: 40 CFR §82.156, “Table 1—Required Levels of Evacuation for Appliances [Except for small appliances, MVACs, and MVAC-like appliances]”

## 2. Phytoplankton form the foundation of aquatic food webs. What have scientists demonstrated about the effect of ozone depletion on phytoplankton?
- A. Production increases because of extra sunlight
- B. Production is directly reduced by increased UVB
- C. They adapt fully with no change in survival
- D. They are unaffected because water blocks UVB

Answer: B. Scientists have shown a direct reduction in phytoplankton production caused by the increased UVB that comes with ozone depletion. UVB also affects their orientation and movement, which lowers their survival. Because phytoplankton are the base of aquatic food webs, this harm can have consequences for the wider marine food chain. More sunlight does not help them, and the upper water layer where they live is not shielded from UVB.
Source: EPA, Health and Environmental Effects of Ozone Layer Depletion, “Scientists have demonstrated a direct reduction in phytoplankton production due to ozone depletion-related increases in UVB.”

## 3. A customer asks a technician to remove the R-12 from an older system and simply charge in a substitute refrigerant with no other changes. Which statement about substitute refrigerants is accurate?
- A. R-134a is a true drop-in replacement for R-12 in any system.
- B. Drop-in replacements are allowed only in systems under 50 pounds.
- C. Any HFC blend can be dropped in if the original oil stays.
- D. There are no true drop-in replacements for CFC refrigerants.

Answer: D. The Section 608 material on substitute refrigerants stresses that there are no true drop-in replacements. Switching refrigerants generally calls for other changes, such as checking lubricant compatibility. No single substitute, including R-134a, is a drop-in, and no charge-size rule creates drop-in status.
Source: EPA, Section 608 Test Topics, “Absence of "drop-in" replacements”

## 4. Under the Section 608 rules, what is the largest factory refrigerant charge an appliance can have and still be classified as a small appliance?
- A. 15 pounds
- B. 50 pounds
- C. 200 pounds
- D. 5 pounds

Answer: D. A small appliance is one that is fully manufactured, charged and hermetically sealed in a factory with five pounds or less of refrigerant. The 15-, 50- and 200-pound figures are thresholds from other rules: system-dependent recovery equipment, leak repair, and the Table 1 evacuation levels.
Source: 40 CFR §82.152, “Small appliance means any appliance that is fully manufactured, charged, and hermetically sealed in a factory with five (5) pounds or less of refrigerant”

## 5. An apprentice tells a technician that only man-made chemicals such as refrigerants can be toxic. Which EPA statement corrects the apprentice?
- A. Only refrigerants containing chlorine can have toxic effects
- B. Water and oxygen can have toxic effects in extreme quantities
- C. Only flammable refrigerants can have toxic effects
- D. Natural substances cause no toxic effects in any quantity

Answer: B. EPA notes that toxic effects have been seen for common substances such as water, table salt, oxygen and carbon dioxide in extreme quantities. Toxicity depends on the amount, not on whether a substance is man-made. Toxicity is not limited to chlorine-containing or flammable substances.
Source: EPA SNAP, Refrigerant Safety, “Toxic effects have been observed for such common substances as water, table salt, oxygen, and carbon dioxide in extreme quantities.”

## 6. A landfill operator accepts a window air conditioner that no longer holds a charge and uses a signed statement as verification. What information must the signed statement include?
- A. Name and address of the recoverer and the date of recovery
- B. Model number of the appliance and the landfill's name
- C. Serial number of the recovery machine and the refrigerant weight
- D. Technician certification number and the refrigerant type

Answer: A. A signed statement used by the final processor must include the name and address of the person who recovered the refrigerant and the date the refrigerant was recovered. The rule does not require the recovery machine serial number, refrigerant weight or appliance model number. A certification number is not required either, because people recovering refrigerant from small appliances for disposal do not have to be certified technicians.
Source: 40 CFR §82.155, “If using a signed statement, it must include the name and address of the person who recovered the refrigerant and the date the refrigerant was recovered.”

## 7. A technician tells a coworker that R-12 vented from a small appliance harms only the ozone layer. Which additional effect of released CFCs does EPA describe?
- A. CFCs break down quickly into harmless water vapor
- B. CFCs turn into HFCs in the lower atmosphere
- C. CFCs persist for a long time as greenhouse gases
- D. CFCs settle out of the air as acid rain

Answer: C. EPA explains that the same high stability that lets CFCs carry chlorine up to the stratosphere also gives them long atmospheric lifetimes. Because they last so long, they keep acting as greenhouse gases. CFCs are stable, so they do not break down quickly, and EPA says nothing about them forming acid rain or turning into HFCs.
Source: EPA SNAP, Refrigerant Safety, “The high stability of CFCs enables them to deliver ozone-depleting chlorine to the stratosphere. The same stability prolongs their atmospheric lifetimes, and thus their persistence as greenhouse gases.”

## 8. On a 70-pound R-22 system, a technician replaces a leaking service valve and also changes the filter drier. How must the service record describe this work?
- A. It must list only the part numbers and serial numbers installed
- B. It must list only the total labor hours charged for the visit
- C. It must list only the part that was leaking and the leak location
- D. It must list each part serviced and the type of work done on each part

Answer: D. The record must identify the parts of the appliance that were serviced or repaired and the type of work performed on each part. Both the valve and the filter drier must therefore be listed, along with what was done to each. Labor hours and part or serial numbers are not what the rule requires, and listing only the leaking part leaves out other work performed.
Source: 40 CFR §82.157, “(iii) The part(s) of the appliance being maintained, serviced, repaired, or disposed;”

## 9. A technician reads 70 psig on a high-pressure system and needs the absolute pressure in psia. What is the absolute pressure?
- A. 99.9 psia
- B. 70.0 psia
- C. 84.7 psia
- D. 55.3 psia

Answer: C. Converting gauge pressure to absolute pressure means adding 14.7. So 70 psig plus 14.7 equals 84.7 psia. Subtracting 14.7 gives 55.3, which is wrong. Leaving the reading unchanged ignores atmospheric pressure. Adding 29.9 confuses psi with inches of mercury.
Source: EPA, Section 608 Test Topics, “Pressure-temperature relationships of common high-pressure refrigerants [may use standard temperature-pressure chart--be aware of need to add 14.7 to translate pounds per square inch gauge (psig) to pounds per square inch absolute (psia)]”

## 10. A replacement component needed to repair a leaking 150-pound R-22 supermarket system is not available within 30 days. No industrial process shutdown is required. What is the maximum time allowed, counted from the date the appliance exceeded the leak rate?
- A. 270 days
- B. 365 days
- C. 180 days
- D. 120 days

Answer: C. When parts are unavailable, repairs may continue until 30 days after the parts are delivered. This extension cannot exceed 180 days from the date the appliance exceeded the leak rate. The 270-day limit applies only when an industrial process shutdown is required. 120 days is the shutdown repair period, and 365 days matches the retrofit timeline.
Source: 40 CFR §82.157, “Additional time is permitted up to 30 days after receiving delivery of the necessary components, not to exceed 180 days (or 270 days if an industrial process shutdown is required) from the date the appliance exceeded the applicable leak rate.”

## 11. Besides removal of certain components, a repair is also major if it uncovers an opening of a certain flow area for a certain time. Which pair matches the definition?
- A. More than 15 square inches for more than 4 minutes
- B. More than 4 square inches for more than 15 minutes
- C. More than 4 square inches for more than 60 minutes
- D. More than 2 square inches for more than 30 minutes

Answer: B. A repair is major when it uncovers an opening of more than four square inches of flow area for more than 15 minutes. Swapping the two numbers or using other figures does not match the definition. The 15 in the rule is minutes, not square inches.
Source: 40 CFR §82.152, “any maintenance, service, or repair that involves uncovering an opening of more than four (4) square inches of “flow area” for more than 15 minutes.”

## 12. A 300-pound R-11 chiller classified as industrial process refrigeration exceeded its trigger rate. What leak inspection schedule applies afterward?
- A. Once every three months until four quarters in a row stay below the rate
- B. Once per month until two months in a row stay below the rate
- C. Once per calendar year until one year stays below the applicable rate
- D. Once every six months until two years stay below the applicable rate

Answer: C. Industrial process refrigeration appliances with a full charge of at least 50 but less than 500 pounds need a leak inspection once per calendar year. Inspections continue until leak rate calculations show the appliance has not exceeded the applicable rate for one year. The quarterly schedule applies only to commercial and industrial process appliances of 500 pounds or more.
Source: 40 CFR §82.157, “(ii) For commercial refrigeration and industrial process refrigeration appliances with a full charge of 50 or more pounds but less than 500 pounds, leak inspections must be conducted once per calendar year until the owner or operator can demonstrate through the leak rate calculations required under paragraph (b) of this section that the appliance has not leaked in excess of the applicable leak rate for one year.”

## 13. A technician has just reached the required recovery vacuum on a low-pressure chiller. What should the technician do next?
- A. Open the chiller at once to save time
- B. Break the vacuum with nitrogen right away
- C. Add 5 psig of vapor to protect the tubes
- D. Wait a few minutes to see if the pressure rises

Answer: D. After reaching the required vacuum, the technician should wait a few minutes and watch for a pressure rise. A rise means liquid refrigerant is still in the system or in the oil, so more recovery is needed. Opening at once or breaking the vacuum right away could release that remaining refrigerant.
Source: EPA, Section 608 Test Topics, “Need to wait a few minutes after reaching required recovery vacuum to see if system pressure rises (indicating that there is still liquid refrigerant in the system or in the oil)”

## 14. An engineer is planning ventilation for a room where a flammable substitute refrigerant will be handled and looks up its lower and upper flammability limits. How does EPA say these limits are used?
- A. To set the maximum leak test pressure for chillers
- B. To set the time-weighted chronic exposure limit
- C. To set how often the purge unit may run
- D. To set guidelines for safe handling, including ventilation

Answer: D. The flammability limits define the range of concentrations in which a substance can burn in air. EPA says they establish safe-handling guidelines, specifically for assessing ventilation requirements. Chronic exposure limits are based on toxicity, and leak test pressure and purge operation are unrelated to flammability limits.
Source: EPA SNAP, Refrigerant Safety, “These limits therefore define the range of concentrations in which the substance is flammable in air and establish guidelines for safe handling, specifically in assessing ventilation requirements for the handling of gases and vapors.”

## 15. A technician will make a non-major repair on an R-123 chiller. The owner plans to have the chiller evacuated to the atmosphere after the repair is completed. What evacuation is required before the chiller is opened?
- A. Pressurize it to no higher than 0 psig
- B. Evacuate it to 25 mm Hg absolute
- C. Evacuate it to the lowest level that avoids contamination
- D. Evacuate it to no higher than 5 psig

Answer: B. The 0 psig allowance applies only when the repair is non-major and the appliance will not be evacuated to the atmosphere afterward. Because this chiller will be evacuated to the atmosphere, the allowance is lost and the full Table 1 level of 25 mm Hg absolute applies. The 5 psig figure is only for oil changes. The lowest-attainable level is only for leaking components.
Source: 40 CFR §82.156, “(1) If evacuation of the appliance to the atmosphere is not to be performed after completion of the maintenance, service, or repair, and if the maintenance, service, or repair is not major as defined at § 82.152, the appliance must:”