# Refrigerant Leak Repair Rules: Thresholds, Rates and Deadlines

> Owners must repair leaks once an appliance's annual leak rate passes 20% for commercial refrigeration, 30% for industrial process refrigeration or 10% for comfort cooling and other equipment, within 30 days (120 if an industrial process shutdown is needed). Under 40 CFR 82.157 these rules cover appliances with 50 pounds or more of ozone-depleting refrigerant, and since January 1, 2026, 40 CFR 84.106 applies the same rates to most appliances with 15 pounds or more of HFCs, except residential and light commercial AC and heat pumps.

Source page: https://clinchedprep.com/blog/refrigerant-leak-repair-rules/
Last reviewed: 2026-11-08

Leak repair becomes mandatory when an appliance's annual leak rate goes over 20% for commercial refrigeration, 30% for industrial process refrigeration, or 10% for comfort cooling and everything else.[1] Those three numbers are on the Type II and Type III exams, and EPA lists leak repair rates and recordkeeping as test topics for both.[6] What changed recently is which equipment they apply to. As of 2026 there are two parallel rules, one for ozone-depleting refrigerants and one for HFCs.

## Two rules, two charge sizes

The original leak repair rule is 40 CFR 82.157. It was briefly extended to HFCs in 2016, but EPA rescinded that extension effective April 10, 2020.[4] Today 82.157 applies only to appliances with a full charge of 50 pounds or more of a class I or class II refrigerant (a CFC or HCFC such as R-22) or a blend containing one.[1]

The newer rule is 40 CFR 84.106, adopted under the American Innovation and Manufacturing (AIM) Act in October 2024 and in force since January 1, 2026.[3][5] It covers appliances with a full charge of 15 pounds or more of an HFC, or of a substitute with a global warming potential above 53.[3]

| | 40 CFR 82.157 | 40 CFR 84.106 |
|---|---|---|
| Refrigerants | CFCs, HCFCs and blends containing them | HFCs and substitutes with GWP above 53 |
| Charge threshold | 50 lb or more | 15 lb or more |
| In effect | Since January 1, 2019 (current scope since April 10, 2020) | Since January 1, 2026 |
| Excluded | Appliances with only substitute refrigerants | ODS-only appliances, residential and light commercial AC and heat pumps |

Sources for the table are 40 CFR 82.157(a) and 84.106(a).[1][3]

The residential exclusion matters. A 4-ton R-410A heat pump is outside both rules. A 40-pound HFC walk-in cooler system at a restaurant, which was outside federal leak repair from 2020 through 2025, is now inside it.

There is one pending change. In May 2026 EPA proposed removing road and intermodal container transport refrigeration units from the HFC leak repair rule, saying it never meant to include them.[5] As of November 2026 that is still a proposal.

## The leak rate triggers

Both rules use the same three rates.[1][3]

| Appliance type | Leak rate that triggers repair |
|---|---|
| Commercial refrigeration (supermarkets, restaurants, cold storage) | 20% |
| Industrial process refrigeration (chemical, pharmaceutical, ice rinks, industrial ice machines) | 30% |
| Comfort cooling and all other covered appliances | 10% |

Part 84 adds refrigerated transport to the 10% group.[3] An appliance that serves both industrial process refrigeration and other uses counts as industrial process refrigeration if at least half its operating capacity goes to the industrial process.[2]

## How the leak rate is calculated

The owner or operator has to calculate the leak rate every time refrigerant is added, unless the addition follows a retrofit or new installation or qualifies as a seasonal variance.[1] The technician who adds or removes refrigerant must hand the owner a service record with the appliance, date, work done, the tech's name, and the amount and type of refrigerant.[1]

EPA allows two methods, and a facility has to use the same one for every covered appliance on site.[2]

### Annualizing method

Divide the pounds added by the full charge. Divide the days since the last addition (or 365, whichever is shorter) by 365. Divide the first number by the second and multiply by 100.[2]

Say a technician adds 4 pounds to a 60-pound R-22 comfort cooling system, and the last addition was 60 days ago. The first step gives 4 ÷ 60, or 0.067. The second gives 60 ÷ 365, or 0.164. Dividing 0.067 by 0.164 gives about 0.41, so the leak rate is roughly 41%, four times the 10% trigger. A small top-off on a short interval can produce a big annualized rate, which is exactly the point of the method.

### Rolling average method

Add up every pound added over the past 365 days, or since the last successful follow-up verification test if that was more recent. Divide by the full charge and multiply by 100.[2]

For HFC appliances under Part 84, the first calculation after January 1, 2026 uses 365 days as the time since the last addition if you're annualizing, or counts only refrigerant added since January 1, 2026 if you're using a rolling average.[3]

**The clock starts when refrigerant is added.** The 30-day repair window runs from the day refrigerant goes into an appliance that is over its leak rate, not from the day someone notices the bill.


## What has to happen once the rate is exceeded

Leak inspection: A certified technician inspects the appliance to find the leak locations.
Repair within 30 days: Repairs must bring the leak rate below the trigger, within 30 days of the refrigerant addition, or 120 days if an industrial process shutdown is required.
Initial verification test: Done within the same 30 or 120 days. If the system was opened and evacuated, the test happens before any refrigerant goes back in.
Follow-up verification test: Done within 10 days of a successful initial test, or within 10 days of the system returning to normal operating conditions if it was evacuated.
Ongoing inspections: Large commercial and industrial systems are inspected every quarter, and everything else once a year, until the leak rate stays under the trigger.


Each step comes from 82.157(d), (e) and (g), and Part 84 repeats them for HFC appliances.[1][3]

### Inspection frequency after a leak

For commercial refrigeration and industrial process refrigeration with 500 pounds or more, inspections are quarterly until the appliance stays under its leak rate for four quarters in a row.[1] Smaller commercial and industrial systems and all comfort cooling systems are inspected once a year until they go a full year under the rate.[1] An automatic leak detection system that is audited or calibrated every year can replace those inspections for the parts of the appliance it monitors.[1]

Under Part 84, commercial and industrial refrigeration systems with 1,500 pounds or more of HFC refrigerant must have automatic leak detection. New systems need it within 30 days of installation, and systems installed from January 1, 2017 through 2025 have until January 1, 2027.[3]

### Extensions

Owners can get more than 30 days in limited cases, such as radiological contamination, other laws that make a 30-day repair impossible, or parts that aren't available. The parts extension runs up to 30 days after the parts arrive, capped at 180 days from the date the appliance went over its leak rate (270 days with an industrial process shutdown).[1] The owner must request the extension from EPA within the original 30 or 120 days.[1]

## When repair isn't the answer

If the owner chooses not to repair, doesn't act at all, or repairs but can't get the rate under the trigger, they must write a retrofit or retirement plan within 30 days.[1] The plan has to be signed by a company official, kept at the site, and carried out within one year.[1]

Appliances that leak 125% or more of their full charge in a calendar year are "chronic leakers." The owner must report them to EPA by March 1 of the following year.[1][3]

Owners must keep leak repair records for at least three years, and full charge records until three years after the appliance is retired.[1]

## How this shows up on the exam

Type II and Type III questions on leak repair test the three trigger rates, the 30-day repair window, verification tests, and who keeps which records.[6] Learn the numbers as a set. That means 20, 30 and 10 percent, 30 and 120 days, 10 days for the follow-up test, 50 pounds for ozone-depleting refrigerants and 15 pounds for HFCs. For the rest of the Type II numbers, see the [recovery and evacuation levels chart](/blog/refrigerant-recovery-evacuation-levels/), and for the full exam layout read the [EPA 608 exam guide](/exams/epa-608/).

## FAQ

### What are the EPA leak rate thresholds?
The trigger rates are 20% per year for commercial refrigeration, 30% for industrial process refrigeration, and 10% for comfort cooling and other appliances. They apply to appliances with 50 pounds or more of ozone-depleting refrigerant under 40 CFR 82.157, and since January 1, 2026 to most appliances with 15 pounds or more of HFCs under 40 CFR 84.106.

### How long do you have to repair a refrigerant leak?
Leaks must be found and repaired within 30 days of the refrigerant addition that showed the appliance over its leak rate, or 120 days if repair requires an industrial process shutdown. An initial verification test is due within the same window and a follow-up test within 10 days after that.

### Do leak repair rules apply to residential air conditioners?
Generally no. The federal leak repair rules start at 50 pounds for ozone-depleting refrigerants and 15 pounds for HFCs, and the 2026 HFC rule specifically excludes residential and light commercial air conditioning and heat pumps. Venting is still illegal on every system, regardless of size.

### How do you calculate a refrigerant leak rate?
With the annualizing method, divide the pounds added by the full charge, divide the days since the last addition (capped at 365) by 365, divide the first result by the second and multiply by 100. The rolling average method adds up all refrigerant added over the past 365 days and divides it by the full charge.


## Sources

1. 40 CFR 82.157 Appliance maintenance and leak repair, Electronic Code of Federal Regulations. https://www.ecfr.gov/current/title-40/chapter-I/subchapter-C/part-82/subpart-F/section-82.157
2. 40 CFR 82.152 Definitions (leak rate), Electronic Code of Federal Regulations. https://www.ecfr.gov/current/title-40/chapter-I/subchapter-C/part-82/subpart-F/section-82.152
3. 40 CFR Part 84, Subpart C: Management of Regulated Substances, Electronic Code of Federal Regulations. https://www.ecfr.gov/current/title-40/chapter-I/subchapter-C/part-84/subpart-C
4. Regulatory Updates: Section 608 Refrigerant Management Regulations, U.S. Environmental Protection Agency. https://www.epa.gov/section608/regulatory-updates-section-608-refrigerant-management-regulations
5. Regulatory Actions for Managing HFC Use and Reuse, U.S. Environmental Protection Agency. https://www.epa.gov/climate-hfcs-reduction/regulatory-actions-managing-hfc-use-and-reuse
6. Section 608 Technician Certification Test Topics, U.S. Environmental Protection Agency. https://www.epa.gov/section608/section-608-technician-certification-test-topics